The EL3314-0092 analog input terminal facilitates the direct connection of four thermocouples in a 2-wire configuration. The channels are electrically isolated from each other and from the E-bus, which effectively prevents adverse effects and damage due to cross currents. Various types of thermocouples are supported, and voltage-to-temperature conversions take place within the terminal. The terminal also allows for mV measurements. Wire breaks are signaled by error-LEDs, as well as on the fieldbus. Cold junction compensation is carried out by an internal precise temperature measurement at the connection terminals; however, operation with an external cold junction is also possible.
The EL3314-0092 also supports TwinSAFE SC (TwinSAFE Single Channel). This enables the use of standard signals for safety tasks in any networks or fieldbuses.
Product status:
regular delivery
Product information
| Technical data | EL3314-0092 |
|---|---|
| Number of inputs | 4 |
| Power supply | via the E-bus |
| Distributed clocks | – |
| Input filter limit frequency | typ. 1 kHz |
| Connection method | 2-wire |
| Conversion time | approx. 2.4 s up to 4 ms, depending on configuration and filter setting, default: approx. 120 ms |
| Voltage measurement | ±78 mV, ±2,5 V |
| Resolution | 24 bit, presentation adjustable: 0.1/0.01/0.001°C or 1 µV per digit |
| Temperature measurement (thermocouple) | type B, C, E, J, K, L, N, R, S, T, U (default setting: type K) |
| Measurement uncertainty (temperature measurement) | at 23°C ambient temperature, with internal cold junction, according type: B: ±2.2°C; C: ±2.4°C; E: ±1.8°C; J: ±1.9°C; K: ±1.9°C; L: ±1.8°C; N: ±1.9°C; R: ±2.1°C; S: ±2.1°C; T: ±1.8°C; U: ±1.8°C; for further details see documentation |
| Measurement uncertainty (voltage measurement) | at ±78 mV, 23°C ambient temperature: < ±0.06% (relative to full scale value) |
| Electrical isolation | 2500 V functional isolation (test voltage channel/channel and channel/fieldbus, production test) |
| Current consumption E-bus | typ. 200 mA |
| Current consumption power contacts | – |
| Special features | channel by channel wire break detection, internal and external cold junction, firmware filter adjustable, simultaneous measurement of the channels, TwinSAFE SC |
| Weight | approx. 60 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE |
| Housing data | EL-12-8pin |
|---|---|
| Design form | compact terminal housing with signal LEDs |
| Material | polycarbonate |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Marking | labeling of the BZxxxx series |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
| Stripping length | 8…9 mm |
| Current load power contacts | Imax: 10 A |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |