The EPX2004-0022 EtherCAT Box enables direct connection of intrinsically safe actuators from zone 0/20 and 1/21 hazardous areas. The EPX2004-0022 supplies an output voltage of 24 V DC and a maximum output current of 50 mA per channel, the sum current is 200 mA. The signal state of the individual channels is indicated by an LED.
Product status:
product announcement | estimated market release 2nd quarter 2025
Product information
Technical data | EPX2004-0022 |
---|---|
Protocol | EtherCAT |
Bus interface | 2 x M8 socket, 4-pin, a-coded, shielded |
Number of outputs | 4 |
Output connections | M12 x 1, 5-pin, a-coded |
Connection method | 2-wire |
Open circuit voltage | 24 V DC |
Load voltage | load-dependent (Ri = 227 Ω) |
Load type | ohmic, inductive, capacitive |
Max. output current | 50 mA per channel |
Sensor supply | from load supply voltage UP |
Current consumption from US | 35 mA |
Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Weight | approx. 300 g |
Operating temperature | -25…+70°C |
Storage temperature | -40…+85°C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL, Ex, IECEx (in preparation) |
Housing data | 16 x M8, 8 x M12 |
---|---|
Dimensions (W x H x D) | 60 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3; 2 fixing holes 4.5 mm diameter for M4 |