The EJ9404 EtherCAT plug-in module is used in combination with the EJ1101-0022 EtherCAT Coupler to supply the E-bus with power. Data is exchanged between the coupler and the module over the E-bus. Each EtherCAT plug-in module draws a certain amount of current from the E-bus (see “Current consumption E-bus” in the technical data). This current is fed into the E-bus by the power supply plug-in module. The maximum output current is 12 A.
Product status:
regular delivery
Product information
| Technical data | EJ9404 |
|---|---|
| Technology | power supply module for E-bus |
| Short-circuit proof | – |
| Input voltage | 24 V DC (-15%/+20%) |
| Output voltage | – |
| Max. output current | 12 A |
| Current consumption E-bus | – |
| Current consumption from US | 10 mA + (∑ E-bus current/6.25) |
| Electrical isolation | – |
| Diagnostics in the process image | – |
| Weight | approx. 50 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. | IP20/see documentation |
| Approvals/markings | CE, UL |
| Housing data | EJ_24_2x16pin_Code78 |
|---|---|
| Design form | EtherCAT I/O plug-in module |
| Material | polycarbonate |
| Installation | on signal distribution board |
| Mechanical coding | EJ plug-in module: signal-specific coding pins on the housing, signal distribution board: holes in the printed circuit board |
| Position of the coding pins | 7, 8 |
| Locking | latching lug in circuit board cut-out |
| Connection method | field wiring: application-specific wiring level on the signal distribution board,
EJ plug-in module: 2 x 20-pin socket strip |
| Dimensions (W x H x D) | 24 mm x 66 mm x 55 mm |
Loading content ...
Loading content ...
Loading content ...
Loading content ...
© Beckhoff Automation 2025 - Terms of Use