The IL2302-Cxxx PLC Box modules combine four digital inputs and four digital outputs in one device. The outputs handle load currents of up to 0.5 A, are short-circuit proof and protected against inverse polarity. The state of each signal is indicated by means of light emitting diodes. The signals are connected M12 screw type connectors.
Product status:
service phase | Possibly with other technical features or equipment in case of a service order or repair. Recommended alternative: ${Life_cycle_alternative_product_list}
Product information
| Technical data digital inputs/outputs | IL2302-Cxxx | 
|---|---|
| Specification | EN 61131-2, type 2 | 
| Number of channels | 4 inputs + 4 outputs | 
| Input/output connections | M12, screw type | 
| Input filter | 3.0 ms | 
| “0” signal voltage | -3…+5 V | 
| “1” signal voltage | 11…30 V, 6 mA input current (EN 61131-2, type 2) | 
| Sensor supply | from control voltage, max. 0.5 A, short-circuit proof in total | 
| Load type | ohmic, inductive, lamp load | 
| Rated load voltage | 24 V DC (-15%/+20%) | 
| Max. output current | 0.5 A per channel, individually short-circuit proof | 
| Short-circuit current | typ. 1.5 A | 
| Auxiliary power current | typ. 20 mA | 
| Current consumption from US | see documentation | 
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded | 
| Bit width in the process image | 4 inputs + 4 outputs | 
| Electrical isolation | channels/control voltage: no, between the channels: no, control voltage/fieldbus: depends on the bus system | 
| Special features | IP-Link coupler | 
| Technical data | IL2302-C900 | 
|---|---|
| Extension modules | max. 120 with max. 512 byte input and 512 byte output data | 
| Digital peripheral signals | max. 964 inputs and 964 outputs | 
| Analog peripheral signals | max. 127 inputs and 127 outputs | 
| Protocol | TwinCAT ADS, Modbus TCP, Beckhoff real-time Ethernet (only IL230x-B90x) | 
| Configuration | via KS2000 | 
| Data transfer rates | 10/100 Mbit/s, automatic recognition of the transmission rate | 
| Bus interface | 1 x RJ45 socket | 
| Data transfer medium | Industrial Ethernet cable (Cat.5), 100 MBaud | 
| Power supply | control voltage: 24 V DC (-15%/+20%); load voltage: according to I/O type | 
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded | 
| Box supply current | 30 mA + current consumption of sensors, max. 0.5 A | 
| Auxiliary power current | according to I/O type | 
| Electrical isolation | control voltage/fieldbus: no, control voltage/inputs or outputs: according to I/O type | 
| Topology | star over Ethernet hub or Ethernet Switch | 
| Distance between stations | 100 m (between hub/switch and Ethernet I/O module) | 
| Weight | approx. 250 g | 
| Operating temperature | 0…55°C | 
| Storage temperature | -25…+85°C | 
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable | 
| Approvals/markings | CE, UL | 
| Housing data | XXL housing | 
|---|---|
| Dimensions (W x H x D) | 30 mm x 210 mm x 26.5 mm | 
| Material | PA6 (polyamide) | 
| Installation | 2 fixing holes 3.5 mm diameter for M3 | 