The EL4072, EL4074, and EL4078 analog output terminals output 10 V/20 mA standard signals with 16-bit resolution and up to 2000 values per second. Each channel can be parameterized individually via the controller/TwinCAT. All common standard signals in the range of ±10 V and ±20 mA can be output per channel – for example, 0…10 V and 4…20 mA. Each channel signals a short circuit for voltage output or a wire break for current output. The current outputs can also drive high burden resistors.
The outputs are designed as single-ended, which means that one connection point of each channel is already connected in the terminal to +24 V or GND and no longer needs to be wired separately.
The EL4072 and EL4074 have 24 V/0 V contacts for the supply of the actuators. With a technical output range of ±107% of the nominal range, the channels can even transport unconventional setpoints, such as for error reporting purposes.
Special features:
- combined output terminal: 10 V/20 mA
- 107% measurement/output range
- high output power at 20 mA: load up to 750 Ω
- 2 ksps conversion rate per channel for standard automation tasks
- output diagnosis (short circuit at voltage output, wire break at current output)
Product status:
regular delivery
Product information
| Technical data | Analog output |
|---|---|
| Number of outputs | 4 |
| Wiring | 2-wire |
| Ground reference (input) | single-ended |
| Max. sampling rate | min. 500 µs (max. 2 ksps) per channel |
| Sampling type | multiplex, approx. 25 µs delay between channels n/n+1 |
| Load | voltage: > 5 kΩ (short-circuit-proof) current: < 500 Ω |
| Output range, nominal | -10/0…+10 V | -20/0/+4…+20 mA |
| Output range, technical | -10.73…+10.73 V | -21.47…+21.47 mA |
| Resolution | 16 bit (incl. sign) |
| Measurement error/uncertainty | typ. < ±0.07%AEW (voltage and current, at 25°C ±5°C, otherwise < ±0.1%) |
| Electrical isolation | Channel/channel | no |
| Technical data | General |
|---|---|
| Power supply | via power contacts, 24 V DC (-15 %/+20 %) |
| Distributed clocks | – |
| Electrical isolation | channel/E-bus: functional separation 707 V DC type test |
| Current consumption power contacts | typ. 60 mA (required for operation of the outputs, specification at full load, additional current requirement at +24 V/0 V connected loads) |
| Current consumption E-bus | typ. 110 mA |
| Special features | U/I parameterizable, ExtendedRange 107%, output diagnosis |
| Weight | approx. 65 g |
| Operating temperature | -25…+55°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE |
| Housing data | EL-12-16pin |
|---|---|
| Design form | HD (High Density) housing with signal LEDs |
| Material | polycarbonate |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Marking | labeling of the BZxxxx series |
| Wiring | solid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver |
| Connection cross-section | s*: 0.08…1.5 mm², st*: 0.25…1.5 mm², f*: 0.14…0.75 mm² |
| Connection cross-section AWG | s*: AWG28…16, st*: AWG22…16, f*: AWG26…19 |
| Stripping length | 8…9 mm |
| Current load power contacts | Imax: 10 A |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
*s: solid wire; st: stranded wire; f: with ferrule