EL3361-0100 | EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 10 V DCNew

Image similar, may contain optional accessories
EL3361-0100 | EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 10 V DC

EL3361-0100 | EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 10 V DC

Run
Steady
Warning
Error
Power
Power contact
+24 V DC
Power contact 0 V
+UBridge
+USense
+UExc
-UBridge
-USense
-UExc
Image similar, may contain optional accessories
EL3361-0100 | EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 10 V DC

EL336x, EL336x-0100: EtherCAT Terminals for multi-channel measuring bridge detection with integrated power supply.

EL3361-0100 | EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 10 V DC

EL3361-0100 | EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 10 V DC

EL3361-0100 | EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 10 V DC

EL336x, EL336x-0100: EtherCAT Terminals for multi-channel measuring bridge detection with integrated power supply.

EtherCAT Terminals for the connection of load cells

EtherCAT Terminals for the connection of load cells

The EL3361-0100 analog input terminal enables the direct connection of a resistor bridge (strain gauge) or a load cell using a 4-wire or 6-wire connection technique. It processes the ratio of the bridge voltage UBridge to the supply voltage USense and outputs the final load value as a process value based on the terminal settings. This enables precise recording of weights, torques, and vibrations with a sampling rate of 10,000 samples per second. The integrated bridge supply is generated from the 24 V of the power contacts.

Product status:

product announcement | estimated market release 2nd quarter 2025

Product information

Technical dataAnalog input
Number of inputs2, for 1 resistor bridge in full bridge technology
Functionresistance bridge, strain gauge (SG), voltage measurement
Wiring4-wire, 6-wire
Ground reference (input)differential
Max. sampling rate10 kSps
Sampling typesimultaneous
Internal resistance> 1 MΩ
Supported nominal sensitivity0.5…320 mV/V
Sensor supply10 V DC from power contacts
Measuring range, nominalUSense: ±12 V | UBrdge: ±4 V
Measuring range, technicalUSense: ±12.84 V | UBridge: ±4.28 V
Resolution24 bit
Measurement error/uncertainty< ±0.05%
Electrical isolation channel/channelno
Operating temperature0…55°C
Housing dataEL-12-16pin
Design formHD (High Density) housing with signal LEDs
Materialpolycarbonate
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxxx series
Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²
Connection cross-section AWGs*: AWG28…16,
st*: AWG22…16,
f*: AWG26…19
Stripping length8…9 mm
Current load power contactsImax: 10 A
Dimensions (W x H x D)12 mm x 100 mm x 68 mm

*s: solid wire; st: stranded wire; f: with ferrule