The analog EL3692 input terminal enables direct resistance measurement in nine measuringe ranges from 0…100 mΩ to 0…10 MΩ. The circuitry of the EtherCAT Terminal enables measurement in 2- and 4-wire versions. The EL3692 offers measuring range selection, either automatic or through the controller. Due to the galvanic isolation, a live power object can also be measured in single-channel operation. The EtherCAT Terminal indicates its state through LEDs. Malfunctions such as broken wires are indicated by error LEDs.
This terminal is also available as a variant with an individual calibration certificate. (See related products)
Product status:
regular delivery
Product information
| Technical data | EL3692 | 
|---|---|
| Number of inputs | 2 | 
| Power supply | via the E-bus | 
| Distributed clocks | – | 
| Feed voltage potentiometer | – | 
| Internal resistance | > 100 MΩ | 
| Input filter limit frequency | 100 Hz | 
| Wiring fail indication | yes | 
| Conversion time | typ. 10…400 ms, dependent on measuring range and settings | 
| Measuring range | 100 mΩ, 1 Ω, 10 Ω, 100 Ω, 1 kΩ, 10 kΩ, 100 kΩ, 1 MΩ, 10 MΩ | 
| Range switching | automatic or through control | 
| Resolution | 24 bit | 
| Measurement error/uncertainty | < ±0.5% (relative to the respective full scale value with 4-wire connection) | 
| Electrical isolation | 1500 V (E-bus/field potential) | 
| Current consumption E-bus | typ. 220 mA | 
| Current consumption power contacts | – | 
| Configuration | via the controller | 
| Special features | automatic range selection, pulse and continuous measurement | 
| Weight | approx. 55 g | 
| Operating temperature | -25…+60°C | 
| Storage temperature | -40…+85°C | 
| Relative humidity | 95%, no condensation | 
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. rating/installation pos. | IP20/variable | 
| Approvals/markings | CE, CCC, UL, ATEX, IECEx | 
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc  | 
| Housing data | EL-12-8pin | 
|---|---|
| Design form | compact terminal housing with signal LEDs | 
| Material | polycarbonate | 
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | 
| Side by side mounting by means of | double slot and key connection | 
| Marking | labeling of the BZxxxx series | 
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | 
| Connection cross-section | s*: 0.08…2.5 mm²,  st*: 0.08…2.5 mm², f*: 0.14…1.5 mm²  | 
| Connection cross-section AWG | s*: AWG28…14,  st*: AWG28…14, f*: AWG26…16  | 
| Stripping length | 8…9 mm | 
| Current load power contacts | Imax: 10 A | 
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | 
*s: solid wire; st: stranded wire; f: with ferrule