The EL4072, EL4074, and EL4078 analog output terminals output 10 V/20 mA standard signals with 16-bit resolution and up to 2000 values per second. Each channel can be parameterized individually via the controller/TwinCAT. All known standard signals in the range of ±10 V and ±20 mA can be output per channel – for example, 4…20 mA. The current outputs can also drive high burden resistors and report an overload or wire break or, in the case of a voltage output, a short circuit. The voltage and current outputs are designed as single-ended, which means that one connection point of each channel is already connected in the terminal to +24 V or GND and no longer needs to be wired separately. The EL4072 and EL4074 have 24 V/0 V contacts for the supply of the actuators. With a technical output range of ±107% of the nominal range, the channels can even transport unconventional setpoints, such as for error reporting purposes.
Special features:
- combined output terminal: 10 V/20 mA
 - 107% measurement/output range
 - high output power at 20 mA: load up to 750 Ω
 - 2 ksps conversion rate per channel for standard automation tasks
 - output diagnosis (short circuit at voltage output, wire break at current output)
 
Product status:
regular delivery
Product information
| Technical data | Analog output | 
|---|---|
| Number of outputs | 8 | 
| Wiring | 2-wire | 
| Ground reference (input) | single-ended | 
| Max. sampling rate | min. 500 µs (max. 2 ksps) per channel | 
| Sampling type | multiplex | 
| Load | voltage: > 5 kΩ (short-circuit-proof) current: < 300 Ω  | 
| Output range, nominal | -10/0…+10 V | -20/0/+4…+20 mA | 
| Output range, technical | -10.73…+10.73 V | -21.47…+21.47 mA | 
| Resolution | 16 bit (incl. sign) | 
| Measurement error/uncertainty | typ. < ±0.07%AEW (voltage and current, at 25°C ±5°C, otherwise < ±0.1%) | 
| Electrical isolation | Channel/channel | no | 
| Technical data | General | 
|---|---|
| Power supply | via power contacts, 24 V DC (-15 %/+20 %) | 
| Distributed clocks | – | 
| Electrical isolation | channel/E-bus: functional separation 707 V DC type test | 
| Current consumption power contacts | typ. 60 mA (required for operation of the outputs, specification at full load, additional current requirement at +24 V/0 V connected loads) | 
| Current consumption E-bus | typ. 135 mA | 
| Special features | U/I parameterizable, ExtendedRange 107%, output diagnosis | 
| Weight | approx. 65 g | 
| Operating temperature | -25…+55°C | 
| Storage temperature | -40…+85°C | 
| Relative humidity | 95%, no condensation | 
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | 
| Protect. rating/installation pos. | IP20/variable | 
| Approvals/markings | CE | 
| Housing data | EL-12-16pin | 
|---|---|
| Design form | HD (High Density) housing with signal LEDs | 
| Material | polycarbonate | 
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | 
| Side by side mounting by means of | double slot and key connection | 
| Marking | labeling of the BZxxxx series | 
| Wiring | solid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver | 
| Connection cross-section | s*: 0.08…1.5 mm²,  st*: 0.25…1.5 mm², f*: 0.14…0.75 mm²  | 
| Connection cross-section AWG | s*: AWG28…16, st*: AWG22…16, f*: AWG26…19  | 
| Stripping length | 8…9 mm | 
| Current load power contacts | Imax: 10 A | 
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | 
*s: solid wire; st: stranded wire; f: with ferrule