The EPX3314-0022 EtherCAT Box allows direct connection of thermocouples from zone 0/20 and 1/21 hazardous areas. The EPX3314-0022 circuit can operate sensors in 2-wire technology. Linearization takes place across the entire, freely selectable temperature range. A wire break is signaled by error-LEDs. Cold junction compensation is performed by internal temperature measurement. With the EPX3314-0022, voltage measurement in the mV range is also possible.
Product status:
product announcement | estimated market release 2nd quarter 2025
Product information
Technical data | EPX3314-0022 |
---|---|
Protocol | EtherCAT |
Bus interface | 2 x M8 socket, 4-pin, a-coded, shielded |
Number of inputs | 4 |
Input connections | M12 x 1, 5-pin, a-coded |
Connection method | 2-wire |
Conversion time | 10…5000 ms (adjustable, default: 310 ms) |
Resolution | 16 bit (incl. sign) |
Sensor types | thermocouples type K, J, L, E, T, N, U, B, R, S, C (default: type K) |
Measuring range | depending on sensor; preset is type K: -270…+1370°C, voltage measurement: ±30…±75 mV, for further types and details see documentation |
Measurement error/uncertainty | < ±0.3% (relative to full scale value) |
Input filter | configurable |
Sensor supply | from load supply voltage UP |
Current consumption from US | 30 mA |
Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Special features | integrated limit value monitoring, digital filters and characteristic curve linearization |
Weight | approx. 300 g |
Operating temperature | -25…+70°C |
Storage temperature | -40…+85°C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL, Ex, IECEx (in preparation) |
Housing data | 16 x M8, 8 x M12 |
---|---|
Dimensions (W x H x D) | 60 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3; 2 fixing holes 4.5 mm diameter for M4 |