EPX3314-0022 | EtherCAT Box, 4-channel analog input, temperature, thermocouple, 16 bit, M12, Ex iNew

Image similar, may contain optional accessories
EPX3314-0022 | EtherCAT Box, 4-channel analog input, temperature, thermocouple, 16 bit, M12, Ex i

EPX3314-0022 | EtherCAT Box, 4-channel analog input, temperature, thermocouple, 16 bit, M12, Ex i

EtherCAT signal input
EtherCAT signal output
Labeling areas
Power supply status display:
Box supply (US)
Auxiliary voltage (UP)
Power supply feed
Power supply downstream
connection
EPX3314-0022 | EtherCAT Box, 4-channel analog input, temperature, thermocouple, 16 bit, M12, Ex i

EPX3314-0022 | EtherCAT Box, 4-channel analog input, temperature, thermocouple, 16 bit, M12, Ex i

The EPX3314-0022 EtherCAT Box allows direct connection of thermocouples from zone 0/20 and 1/21 hazardous areas. The EPX3314-0022 circuit can operate sensors in 2-wire technology. Linearization takes place across the entire, freely selectable temperature range. A wire break is signaled by error-LEDs. Cold junction compensation is performed by internal temperature measurement. With the EPX3314-0022, voltage measurement in the mV range is also possible.

Product status:

product announcement | estimated market release 2nd quarter 2025

Product information

Technical dataEPX3314-0022
ProtocolEtherCAT
Bus interface2 x M8 socket, 4-pin, a-coded, shielded
Number of inputs4
Input connectionsM12 x 1, 5-pin, a-coded
Connection method2-wire
Conversion time10…5000 ms (adjustable, default: 310 ms)
Resolution16 bit (incl. sign)
Sensor typesthermocouples type K, J, L, E, T, N, U, B, R, S, C (default: type K)
Measuring rangedepending on sensor; preset is type K: -270…+1370°C, voltage measurement: ±30…±75 mV, for further types and details see documentation
Measurement error/uncertainty< ±0.3% (relative to full scale value)
Input filterconfigurable
Sensor supplyfrom load supply voltage UP
Current consumption from US30 mA
Power supply connectionfeed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Special featuresintegrated limit value monitoring, digital filters and characteristic curve linearization
Weightapprox. 300 g
Operating temperature-25…+70°C
Storage temperature-40…+85°C
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/markingsCE, UL, Ex, IECEx (in preparation)
Housing data16 x M8, 8 x M12
Dimensions (W x H x D)60 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3; 2 fixing holes 4.5 mm diameter for M4