The SinCos module IP5209-Bxxx serves as interface for the direct connection of a measuring sensor, for example a measuring probe with sinusoidal voltage output 1 VPP to the higher-level fieldbus. In contrast to the standard version, instead of a voltage input the special IP5209-Bxxx-1000 version has a current input for 11 µAPP measuring probes. The measuring signal is processed, interpolated and made available as a 32 bit value. The signal period resolution is 10 bits, i.e. 1024 steps. The reference mark is also stored in a 32 bit value. The current count and the reference mark value can be read. The limit frequency for the measuring signal inputs is 100 kHz.
Product status:
regular delivery
Product information
| Technical data position measurement | IP5209-Bxxx |
|---|---|
| Connection technology | M23 connector with outer thread, 12-pin |
| Number of channels | 1 |
| Nominal voltage | 24 V DC (-15%/+20%) |
| Signal input | 1 VPP |
| Encoder supply | 5 V DC |
| Sensor supply | 5 V DC from control voltage, max. 0.5 A |
| Limit frequency | 100 kHz (scanning of the input signals with 500 kHz) |
| Resolution | 10 bit, 1024 steps per period |
| Commands | set count, evaluate reference mark latch, change of direction, frequency control |
| Data transfer rates | – |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Current consumption from US (without sensor current) | 130 mA |
| Bit width in the process image | input/output: 2 x 32 bit data, 1 x 8 bit control/status |
| Electrical isolation | depends on the bus system |
| Technical data | IP5209-B528 |
|---|---|
| Extension modules | – |
| Digital peripheral signals | according to I/O type |
| Analog peripheral signals | according to I/O type |
| Configuration | via KS2000 or the controller (explicit messaging) |
| Data transfer rates | automatic detection up to 500 kbaud |
| Bus interface | 1 x M12 plug, 5-pin, 1 x M12 socket, 5-pin (tee-connector integrated) |
| Data transfer medium | shielded copper cable, with power supply, typ. 2 x 2 x 0.25 mm² |
| Power supply | control voltage: 24 V DC (-15%/+20%); load voltage: according to I/O type |
| Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Box supply current | 45 mA + current consumption of sensors, max. 0.5 A |
| Auxiliary power current | according to I/O type |
| Electrical isolation | control voltage/fieldbus: 500 V, control voltage/inputs or outputs: according to I/O type |
| Distance between stations | 500 m 250 m 100 m |
| Operating modes | bit strobe, polling, cyclic, change of state (COS) |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
| Approvals/markings | CE, UL |
| Housing data | XXL housing |
|---|---|
| Dimensions (W x H x D) | 30 mm x 210 mm x 26.5 mm |
| Material | PA6 (polyamide) |
| Installation | 2 fixing holes 3.5 mm diameter for M3 |
| Ordering information | |
|---|---|
| IP5209-B528 | Fieldbus Box, 1-channel encoder interface, DeviceNet®, SinCos, 1 Vpp, M23, integrated T-connector (service phase) |
| IP5209-B528-1000 | Fieldbus Box, 1-channel encoder interface, DeviceNet®, SinCos, 11 µApp, M23, integrated T-connector (service phase) |